XGN15-12 12KV High Voltage Switchgear for SF6 ring main unit

名称:XGN15-12 12KV High Voltage Switchgear for SF6 ring main unit

供应商:share

价格:面议

最小起订量:0/

地址:FUYUAN INDUSTRIAL,JIUWEI BAOAN,SHENZHEN,P.R.C.

手机:15012562236

联系人:崔海芳 (请说在中科商务网上看到)

产品编号:70915123

更新时间:2021-02-13

发布者IP:183.13.244.11

详细说明

  Specifications

  XGN SF6 12KV and 24KV RUM switch cabinet

  1.Certificate:CCC,CTQC

  2.Top5 in china

  3.ISO9001,ISO14001,OHSAS18001

  Metal Sealing Ring Net Switch Cabinets

  XGN15-12

  XGN15-12 Metal sealing ring net switch equipment (SF6 Ring net cabinet) is a new generation of gives priority to with SF6 load switch switch ring network cabinet, this ark is propped by air insulation canal, sulfur hexafluoride gas do arcing medium;Compact structure is simple, flexible operation, easy installation, with multiple interlocking function.With the mechanism, PT and CT, UPS, DTU can be widely used in power distribution network automation system.Combined with modern sensor technology and the latest protection relay, with its advanced technical performance and lightweight flexible assembly scheme can meet the changing needs of the market.

  Purpose and scope of use

  This ark is propped applied to ac 50 hz or 60 hz, canal of 12 kv power system, is widely used in industrial and civil cable ring network and electrical terminals, the acceptance and distribution of electricity as a.Suitable for urban residential distribution, small secondary

  sub-station, small opening and closing, industrial and mining enterprises, shopping malls, airport, subway, generators, hospital, stadium, railway, tunnel, etc.

  Environmental conditions

  Altitude: <1000 m (if you have any special requirement when ordering)

  Ambient temperature: - 40 °C ~ + 40 °C

  The surrounding relative humidity: day average < 95%, <90% on average

  Ambient air no obvious dust, smoke, corrosive or flammable gases, water vapor or salt pollution;No recurrent violent vibration.

  Technical Parameters

  Name

  Unit

  Parameter

  Rated voltage

  KV

  12

  Rated lightning impulse withstand voltage

  Interphase and relatively

  KV

  75

  Fracture

  KV

  85

  1min Power frequency withstand voltage

  Interphase and relatively

  KV

  42

  Fracture

  KV

  48

  Rated frequency

  HZ

  50/60

  Rated current

  Main bus-bar

  A

  630

  Branch bus

  A

  630

  Rated short-time resistance current

  Primary loop

  KA

  20/3s

  Ground loop

  KA

  20/3s

  Rated current peak tolerance

  KA

  50

  Transfer current

  A

  1500

  Level of protection