详细说明
10MWH system
10MWH subsystem configurations: battery batteries 300AH and 174 300AH batteries connected in series to the battery pack , the battery pack in parallel three groups , received the DC cabinet, and then connect with the bi-directional converter . 10MW system configuration 20 such subsystems.
Basic parameters :
1) 10MWH an energy storage power station , with a total number of 10,440 batteries , model LY-LFP300 lithium battery.
2 ) Discharge time 4 hours , the discharge power 0.25MW; charging time 8 hours , charging power 0.125MW.
3) 500kW DC current cabinet of 20 , 500KW bidirectional converter 20
4 ) battery holder covers ( including aisles ) of approximately 600 square meters.
Run
Energy storage power plants currently in operation mode is 23:00 to 7:00 in the morning to 0.125C rate charge 8 hours during the day to 0.25C discharge rate four hours . Users can be set according to the actual situation , can also be adjusted in real time .
No. Name Quantity Remark
A battery system unit 10MWh including battery pack and BMS
2 500KW bidirectional converter 20 SS500K
3 500KW DC bus cabinet 20 PMD-D500K
4 DC cable for the battery pack to the DC bus between cabinet
5 DC cable to be used between the DC bus converter cabinet
6 BMS 20 sets of monitor battery status