  EL2502 | 2-channel pulse width output terminal 24 V DC

  The EL2502 output terminal modulates the pulse width of a binary signal and outputs it electrically isolated from the E-bus. The mark/space ratio is prescribed by a 16 bit value from the automation unit. The output stage is protected against overload and short-circuit. The EtherCAT Terminal has two channels that indicate their signal state via LEDs. The LEDs are driven in time with the outputs, and show the mark/space ratio by their brightness.

Technical dataEL2502 | ES2502
Connection technologyPWM output, push-pull outputs
Number of outputs2
Rated load voltage24 V DC (-15 %/+20 %)
Load typeohmic, inductive, lamp load
Distributed clocks
Max. output current0.5 A (short-circuit-proof) per channel
Short circuit currenttyp. < 1.5 A
PWM clock frequency20 Hz…20 kHz, 250 Hz default
Base frequency1 Hz…125 kHz, 250 Hz default
Duty factor0…100 % (TON > 750 ns, TOFF > 500 ns)
Resolution9…15 bit
Reverse voltage protectionyes
Current consumption E-bustyp. 150 mA
Electrical isolation500 V (E-bus/field potential)
Current consumption power contactstyp. 30 mA + load
Bit width in the process image2 x 16 bit PWM output
Configurationvia TwinCAT System Manager
Special featuresseparate frequency can be set for each channel
Weightapprox. 50 g
Operating/storage temperature0…+55 °C/-25…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 20/variable
Pluggable wiringfor all ESxxxx terminals
ApprovalsCE, UL, Ex